The short version
- 1Start simple: remote batteries, the wall switch, the MCB and the stabiliser account for many 'dead AC' calls.
- 2An MCB that trips repeatedly is a protection device doing its job. Don't keep resetting it or upgrade it to a bigger one.
- 3Blinking lights on the indoor unit are error codes. Note the pattern before you call; it saves time.
- 4Wait at least 3 minutes after switching off before switching on again. Most ACs protect the compressor with a delay.
It's always the first really hot evening, isn't it? You press the remote, and nothing. Or the AC starts, runs for a minute, and the whole room goes dark as the MCB trips.
Before anything else: don't keep resetting the MCB over and over. It trips for a reason, and repeated resets on a genuine fault can damage the compressor or wiring. Instead, work through these checks.
If the AC won't turn on at all
- 1Check the remote
Replace the batteries. Point a phone camera at the remote's tip and press a button. If you see a flicker on screen, the remote is transmitting.
- 2Check power to the unit
Is the wall switch on? Is the indoor unit's display or standby light glowing? Does the socket work with another appliance?
- 3Check the MCB and stabiliser
Look at the AC's dedicated MCB in the distribution board. Check the stabiliser's display and output. Stabilisers fail too, and they often cut power on low voltage by design.
- 4Wait out the delay
Most ACs wait around 3 minutes before restarting the compressor after being switched off. Give it time before assuming it's dead.
- 5Look for blinking lights
If the indoor unit's LEDs are blinking in a pattern, that's an error code. Count the blinks or photograph the display, and call with that information.
If the MCB keeps tripping
An MCB trips when it sees too much current (an overload or short) or, for RCCBs, current leaking to earth. With ACs, the usual reasons are:
- Compressor struggling to start because of a failed capacitor. It draws a big current and trips the breaker.
- Short circuit or earth leakage from damaged wiring, water getting into the electrical box, or a rodent-chewed cable.
- Undersized wiring or MCB, which is common when an AC is added to an old circuit that also runs other loads.
- Compressor winding fault, the serious one, usually diagnosed with a megger and clamp meter.
- Low voltage, which pushes current up as the compressor tries to deliver the same power.
What the technician will check
Electrical diagnosis
- Supply voltage at the unit, at rest and under load
- Capacitor value measured against its rating
- Compressor winding resistance and insulation (megger test)
- Running and starting current with a clamp meter
- Wiring size, terminals and earth continuity
- PCB, sensors and error code history
Blinking lights and error codes
Every brand has its own code system. Daikin, Voltas, Dunham-Bush and others show codes differently, some on the display and some as blink patterns. Codes commonly point to sensor faults, communication errors between indoor and outdoor units, high-pressure protection or low refrigerant. Note the code, switch off, and call. Guessing and resetting repeatedly rarely helps.
Frequently asked
The AC trips only in the afternoon. Why?
Peak afternoon heat means the highest compressor load, and often the lowest supply voltage too. A weak capacitor, dirty condenser or borderline wiring shows up exactly then. It's worth getting checked before it becomes a full failure.
Do I need a stabiliser for an inverter AC?
Most inverter ACs have a wide operating voltage range built in, and manufacturers often say a stabiliser isn't needed. In areas with frequent, severe fluctuations, a suitable stabiliser is still cheap insurance. Check your model's manual and warranty terms.
